10
―
Measurement of current consumption (ILINE) (Only for M-6202)
Threshold and display (Threshold display is dependent on the accuracy on each
measuring range.)
Reference conditions
Unless otherwise specified, this specification is dependent on following
condition.
(1) Ambient temperature : 23±5℃
(2) Relative humidity : 45 ~ 75%
(3) Position : Horizontal
(4) AC power source : 230V, 50/60Hz
(5) Altitude : 2000m or less
Operating temperature and humidity range
0℃ ~ +40℃ Relative humidity: 85% or less (no condensation)
Storage temperature and humidity range
-20℃ ~ +60℃ Relative humidity: 85% or less (no condensation)
Rate voltage and frequency
Rated voltage : 230V ±10%
Rated frequency : 50 ~ 60Hz ±1%
Operating method : Dual slope integration
Display : 3 1/2 digit in LCD, character height 17mm,
Max reading 1999 with units, symbols, etc.
Maximum rated power
Approx. 9VA
Maximum throughput of M-6202
Max. 4000VA
Rating
Measuring range
Resolution
Accuracy
Throughput
16A AC
0 ~ 15.99A AC
10mA
± (2% rdg+3dgt)
Max. 4000VA
Range
Protective conductor resistance
Insulation resistance
Equivalent leakage current
Contact current
Threshold
LED for threshold
display
Warning buzzer
(continuous sound)
RPE >0.3Ω
RPE >1Ω
RINS < 0.5MΩ
RINS < 2.0MΩ
IEL >7.0mA
IEL >15mA
IL >0.25mA
IL >0.5mA
●
●
●
●
●
●
●
●
---
●
●
---
---
●
---
●
Kommentare zu diesen Handbüchern