Kyoritsu 6016 Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Werkzeug Kyoritsu 6016 herunter. KYORITSU 6016 User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken

Inhaltsverzeichnis

Seite 1 - KEW 6016

INSTRUCTION MANUALMULTI-FUNCTION TESTERKEW 601608-09 92-1959BDISTRIBUTORKyoritsu reserves the rights to change specifications or designs describe

Seite 2 - 21. CASE AND STRAP ASSEMBLY

7Loop impedance, PSC/PFC and RCD testing functions have the following features:Wiring check Three Wiring symbols indicate if the wiring of the

Seite 3

8 5. Specification5.1 Measurement SpecificationContinuityOpen Circuit Voltage (DC)Short CircuitCurrentRange Accuracy5V±20%(*1)Greater than 200mA20/20

Seite 4 - 1. SAFE TESTING

9PSC (L-N/L-L) / PFC (L-PE)FunctionRated VoltageNominal Test Current at 0Ω External Loop:Magnitude/Duration(*5)Range AccuracyPSC100~500V50/60Hz6A/20ms

Seite 5

10RCD Trip Current DurationFunction TypeRCD Trip Current Duration10 30 100 300 500 1000Trip Current Duration(ms)X1/2GAC 2000 2000 2000 2000 2000 2000A

Seite 6 - 2. INSTRUMENT LAYOUT

11Possible number of tests with fresh batteries.Continuity :Approx. 2000 times min. at load 1ΩInsulation Resistance :Approx. 1000 times min. at lo

Seite 7

12Loop Impedance(EN61557-3)VoltOperating range compliant with EN61557-3 operating errorMaximum percentageoperating errorL-PE 0.50~1999Ω±30%L-N 0.50~19

Seite 8 - 3. Accessories

13Earth Resistance (EN61557-5)Operating range compliant with EN61557-5 operating errorMaximum percentage operating error5.00~1999Ω ±30%The influencing

Seite 9 - 4. FEATURES

145.4 Applied standardsInstrument operating Standard IEC/EN61557-1,2,3,4,5,6,7,10Safety standard IEC/EN 61010-1(2001),CATIII (300V) -InstrumentIEC/EN

Seite 10

155.5 List of Display MessageLow battery warningTemperature monitor for internal resistance, available at Loop, PSC/PFC & RCD function. Fu

Seite 11 - 5. Specification

16 6. Configuration Setting for following three parameters● UL value・・・・・・・・Selects a UL value for RCD function● Touch Pad・・・・・・Enables / disables To

Seite 12

Fig.55 Fig.56 Fig.54 Match the hole of the Buckle and the protrusion at the side face of KEW6016, and slide it upwards.Pass the strap belt down thro

Seite 13

17 7. CONTINUITY (RESISTANCE) TESTS WARNINGEnsure that circuits to be tested are not live.Disconnect the instrument from the circuit under test b

Seite 14

184 Operate the Continuity Null (F1) button, this will null out the lead resistance and the indicated reading should go to zero.5 Release the test

Seite 15

197.2 2Ω Buzzer ( ) functionUse F2 Button to enable / disable the 2Ω Buzzer. The buzzer sounds when measured resistance is 2Ω or less while this funct

Seite 16

20 8. INSULATION TESTS WARNING Ensure that circuits to be tested are not live.Disconnect the instrument from the circuit under test before operat

Seite 17

218.1.3 Conduction CurrentSince the insulation resistance is not infinite, a small leakage current flows through the insulation between conductors. Si

Seite 18

22If the circuit has alternating voltage applied, the capacitive current (8.1.2) will always be present and can never be eliminated. This is why a dir

Seite 19 - Back Light :

238.3 Preparation for measurementBefore testing, always check the following:-1 The ‘low battery’ Indication is not displayed2 There is no visually obv

Seite 20 - NULL OFF

244 Attach the test leads to the circuit or the appliance under test (see Figs 20 & 21)5 If the “Live Circuit” warning is displayed on the LCD a

Seite 21 - Measuring

25 WARNING● Never touch the circuit, test lead tips or the appliance under test during insulation testing because high voltages exist. CAUTION● Ne

Seite 22 - 7.2 2Ω Buzzer ( ) function

26 9. LOOP/ PSC/PFC9.1 Principles of measurement of fault loop impedance and PFCIf an electrical installation is protected by over-current protective

Seite 23 - 8. INSULATION TESTS

11. Earth tests ... 43 11.1 Principles o

Seite 24

27According to the International Standard IEC 60364, for TT systems the characteristics of the protective device and the circuit resistance shall fulf

Seite 25

28For this example the max permissible value is 1667 Ω (RCD =30mA and contact voltage limit of 50 V). The instruments reads 12.74 Ω, thus the cond

Seite 26

29According to the International Standard IEC 60364, for TN system the characteristics of the protective device and the circuit impedance shall fulfil

Seite 27

30Protection by gG fuseswith Uo of 230VProtection by MCBs with Uo of 230V(Disconnection time 0.4 and 5s)Rating (A)Disconnection time 5sDisconnection t

Seite 28

31Max value of Zs for this example is 1.44 Ω (MCB 16A, characteristic C), the instrument reads 1.14 Ω (or 202 A on Fault current range) it means that

Seite 29 - 9. LOOP/ PSC/PFC

329.3. Operating instructions for LOOP and PSC/PFC9.3.1 Initial Checks: to be carried out before any testing1. PreparationAlways inspect your test ins

Seite 30

33(3) Press the MODE switch(F1) and select L-N to measure Loop(L-N/L-L) or PSC or select L-PE to measure earth loop impedance or PFC. Di

Seite 31

349.3.2 Measurement of LOOP and PSC/PFCa. Measurement at Mains Socket Outlet Connect the mains test lead to the instrument. Insert the moulded plu

Seite 32

35● Measurement in ATT mode requires longer time than that is required for the other measurements (approx. 7 sec). When measuring a circuit

Seite 33

36PEΩL-PE230V50.0HzL-PEL-N!ATT:ONPSCA230VL-N50.0HzL-PEL-N! Fig.33 Connection for Line – Neutral measurement Fig.34 Connection for Line – Line measurem

Seite 34

1 1. SAFE TESTINGElectricity is dangerous and can cause injury and death. Always treat it with the greatest of respect and care. If you are not quite

Seite 35 - ATT : ON

37 10. RCD TESTS10.1 Principles of RCD MeasurementThe RCD tester is connected between phase and protective conductor on the load side of the RCD afte

Seite 36

38However it is also good practice to consider even more stringent trip time limits, by following the standard values of trip times at I△n defined by

Seite 37

39Practical example of RCD test with distribution leads.10.2 Principles of Uc Measurement Ground being imperfect in the Fig35, when R exists, when

Seite 38

401. Operate the Power button and turn on the instrument. Turn the rotary switch and select the RCD function.2. Press the MODE switch(F1) and sele

Seite 39

413. Voltage MeasurementWhen the instrument is first connected to the system, it will display the line-earth voltage which is updated every 1s.

Seite 40 - 10. RCD TESTS

42therefore, the connection between neutral point of the distribution system and earth should be checked before testing.● If leakage currents flow

Seite 41

43 11. EARTH TESTS11.1 Principles of Earth Measurement This Earth function is to test power distribution lines, in-house wiring system, electrical ap

Seite 42

44Note :● Make sure to stick the auxiliary earth spikes in the moist part of the soil. Give enough water where the spikes have to be stuck into the d

Seite 43

45 12. PHASE ROTATION TESTS1. Operate the Power button and turn on the instrument. Turn the rotary switch and select the PHASE ROTAION functio

Seite 44

46 13. VOLTS 1. Operate the Power button and turn on the instrument. Turn the rotary switch and select the VOLTS function.2. Insert the Test L

Seite 45

211 Do not operate the function selector while the instrument is connected to a circuit. If, for example, the instrument has just completed a contin

Seite 46 - 11. EARTH TESTS

47 16. MEMORY FUNCTIONMeasured result at each function can be saved in the memory of the instrument. (MAX : 1000)16.1 How to save the dataSave the re

Seite 47

48(5) Press OK( ). (Confirmed)(6) Press SAVE(). (Confirmed)(7) “SAVING” is displayed for about 2 sec on the LCD, and then returns to the star

Seite 48 - 12. PHASE ROTATION TESTS

4916.2 Recall the saved dataSave data can be displayed on LCD according to following sequence.(1) Press to enter into MEMORY MODE.(2) Press to enter

Seite 49 - 15. BACK LIGHT

50ALL DELETEDELETE Fig.50-1 Fig.50-2 Fig.50-3 Fig.50-4 ALL DELETEMEMORY MODEESC:MEM BUTTONDELETERECALLSAVEDELETE MODEDATA No.000INSULATION18.52MΩ250VS

Seite 50 - 16. MEMORY FUNCTION

51ALL DELETEDELETE DeletingFig.50-5 Fig.50-6 Fig.50-7 Fig.50-8 Fig.50-9 DELETE MODEDATA No.001?DELETEINSULATION18.52MΩ250VSITE : 01BOARD : 01CIRCUIT :

Seite 51 - Fig.48-6

5216.4 Transfer the stored data to PCThe stored data can be transferred to PC via Optical Adapter Model8212USB (Optional Accessory).●How to transfer t

Seite 52 - Fig.49-3

53 17. GENERAL17.1 If the symbol ( )appears, this means that the test resistor is too hot and the automatic cut out circuits have operated. A

Seite 53 - ALL DELETE

54 18. BATTERY REPLACEMENTWhen the display shows the low battery indication , , disconnect the test leads from the instrument. Remove the battery cov

Seite 54 - ALL DELETEDELETE

55 20. SERVICINGIf this tester should fail to operate correctly, return it to your distributor stating the exact nature of the fault. Before returnin

Seite 55

Fig.55 Fig.56 Fig.54 Match the hole of the Buckle and the protrusion at the side face of KEW6016, and slide it upwards.Pass the strap belt down thro

Seite 56 - 17. GENERAL

3 2. INSTRUMENT LAYOUTName Operation(1) Back Light Button Switches on/off the Backlight of the Display(LCD)(2) Test Button Starts measurements. (pres

Seite 57 - 19. FUSE REPLACEMENT

INSTRUCTION MANUALMULTI-FUNCTION TESTERKEW 601608-09 92-1959BDISTRIBUTORKyoritsu reserves the rights to change specifications or designs describe

Seite 58 - 20. SERVICING

4Input Terminal Function Terminal(1)Terminal Names for :INSULATION, CONTINUITYLOOP,PFC/PSC,RCD,VOLTSL : LinePE : Protective EarthN : Neutral (for LOOP

Seite 59

5 3. Accessories1.Main Test Lead (Model7218) 2.Remote Test Lead (Model 7196) 3.Distribution Board fused test lead (Model7188) (Fuse: 10A/600V fast ac

Seite 60

6 4. FEATURESThe KEW6016 Multi-Function tester performs eight functions in one instrument.1 Continuity tester2 Insulation resistance tester3 Loop imp